Single Phase TOSHIBA 1600XP Series UPS
1600XP Series UPS Tower
Single Phase TOSHIBA 1600XP Series UPS 2
1600XP Series UPS Tower (open)
« »
TOSHIBA 1600XP Series UPS

1600XP Series is single phase UPS, available in 3.6 kVA, 6 kVA, 8 kVA, 10 kVA, 14 kVA, 18 kVA and 22 kVA. This series offers in tower design solution. As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase power to your critical systems while keeping batteries charged continuously, even if the utility power fails. This 1600XP Series will provide you with an additional 20% Extra Power! From a name that is synonymous with quality. This system combines true on-line technology, state of the art electronics and the Toshiba name to offer a high reliability UPS.

Features & Benefits

• NEW User-Friednly, Programmable Touch-Screen Display

• NEW Angled Terminal Block for Ease of Installation

• NEW RoHS and CE Certification

• Hot Swappable Batteries

• Hot Swappable Cooling Fans

• Internal Isolation Transformer

• External Battery Connector

• Wide Input Voltage Window +10% to -30%

• Wide Input Frequency Window 45 to 65 Hz

• True On-Line, Double-Conversion UPS

• Generator Compatible

• Crest Factor 3.0

• Input Current THD < 5%

• Input Power Factor > 0.95

• Power Factor Correction

• 0.85 Output Power Factor

• Opt Network Interface Card

• Opt Env Monitoring Device

static bypass
1600XP Series UPS Technical Specifications (3.6kVA - 22kVA)
CAPACITY 3.6kVA (3.1 KW) 6kVA (5.1 KW) 8kVA (6.8 KW) 10kVA (8.5 KW) 14kVA (11.9 KW) 18kVA (15.3 KW) 22kVA (18.7 KW)
Topology True On-Line, Double Conversion; IGBT Power Factor Corrected Input; Internal Isolation Transformer
Certifications UL 1778, CUL, CE, FCC Class A, IEEE 587, ANSI/C62.41, ISO 9001, ISO 14001, NEMA/PE1-1993, RoHs
INPUT
Voltage Single-Phase 208/240 VAC (Three-Wire Input/L-L, G); 230 VAC (Three-Wire Input/L, N, G), +10% -30% (Based on Typical 70% Load)
Frequency 45 to 65 Hz (Auto-Sensing)
Power Factor >0.95 For All Loads
Current THD <5% (Even for 100% Non-Linear Loads)
AC Input Breaker Rating 30A 50A 60A 63A 100A 100A 125A
OUTPUT
Voltage Single-Phase 240/208/120 VAC (Four-Wire Output/L-L, N, G) 230 VAC (Three-Wire Output L, N, G)
Voltage Regulation ±3%; ±1% Typical
Frequency 50/60 Hz; ±0.5 Hz/1.0 Hz/1.5 Hz (Factory or Authorized Service Center Selectable)
Voltage THD <3% for Linear Load; 1% Typical
Common Mode Noise < 0.5 V RMS
Rated-Load Power Factor 0.85 (0.6 to 1.0) Lag
Rated Output Current @ 240 V 15A 25A 33.3A 41.6A 58A 75A 91.6A
Maximum Peak Output Current 45A 75A 100A 125A 174A 225A 275A
Overload Capacity Inverter Mode: 150% for 10 Seconds, 125% for 30 seconds; Bypass Mode: 125% for 10 Minutes, 1000% for One Cycle
BATTERY
Battery Type Valve-Regulated Lead Acid; Flame Retardant (9.0 Amp Hr)
Backup Time (Fully Charged) 7 Minutes 7 Minutes 7 Minutes 5 Minutes 7 Minutes 5 Minutes 3 Minutes
0.85 Power Factor; 77° F; Approximately 30% More Runtime for Output Power Factor of 0.7 (Triple Backup Time at ½ Load
Recharge Time 24 Hours (Full), 12 Hours (90%)
DC Link 144VDC 216VDC 288VDC
ENVIROMENT
Efficiency (AC-DC-AC) >85%
Temperature Range 0 to 40°C (Operating); -20° to +40°C (Storage)
Heat Generation (BTU/Hr) 1843 3071 4095 5118 7168 9213 11,260
Altitude 6600 Feet (2000 Meters) Maximum Without Derating
Audible Noise <60 DBA @ 1 Meter
MECHANICAL
Enclosure Steel Enclosure; Complies with NEMA 1 and UL Type-1 Standard
Enclosure Dimensions (HxWxD) 22.1” x 10” x 33” 27.5” x 10” x 33” 28.4” x 13” x 34.9” 39.1” x 17.5” x 36.1”
Shipping Weight 280 lb/127 kg 346 lb/157 kg 476 lb/214 kg 784 lb/355 kg 784 lb/355 kg 835 lb/379 kg
Battery Pack Size (HxWxD) 5” x 7.3” x 19” (Battery Pack Part # 51896-FS)
Battery Pack Quantity Two Three Four Eight
ADDITIONAL FEATURES Output Isolation Transformer, RS232 & Dry Contact Interface, Crest Factor of 3, Angled Terminal Blocks for Easy Installation, Casters for Mobility
OPTIONS
SNMP & WEB-Based Monitoring RemotEye® III, RemotRadar™, & Environmental Monitoring Device
WARRANTY Three Years on Electronics (UPS); Two Years on Battery (See Toshiba Warranty Policy for Full Details)
1. Due to continuous product improvements, program specifications are subject to change without notice.