Single Phase TOSHIBA 1800 Series UPS
1800 Series UPS
Single Phase TOSHIBA 1800 Series UPS 2
1800 Series UPS
« »
TOSHIBA 1800 Series UPS

1800 Series is a single phase UPS, available in 2.4kVA. This series offers the tower design solution. As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase power to your critical systems while keeping batteries charged continuously, even if the utility power fails.

Features & Benefits

• True On-Line Double Conversion, PWM Input PF Correction UPS

• Isolation Transformer for Complete Power Conditioning

• High Overload and CF for Motor Type Loads

• Auto-Restart and Cold Start Features for Remote Location

• Increased Input Voltage Window +10% to -40% for Increased Battery Life

• Four (4) Fan Speed for Optimum Cooling and Noise Reduction

• Compactly Designed, Both Rectifier and Inverter Utilized 36.5 kHz IGBT Technology

• Intelligent Charger with Rapid Charge in only 3.5 hours to 90%

• Wide Input Frequency Window for Complete Generator Compatibility

TOSHIBA 1800 Series UPS Technical Specifications
CAPACITY 2400VA
INPUT
Voltage Single-Phase 208/240 Vac (3 Wire Input/L-L,G)
Voltage Range 144 V to 264 V (+10% to -40%)
Frequency 50/60 Hz Auto-Sensing
Synchronization Window ±3Hz
Power Factor Greater than 0.95
OUTPUT
Voltage 120/208/240 Vac (3 Wire Input/L-L,G)
Capacity(VA/W) 2400 VA*/1680 W*
Voltage Regulation ±3%
Synchronization Window ±3Hz
Voltage Distortion Less than 5% THD at Full Non-Linear Load. Less than 3% THD at Full Linear Load.
Step Load ± 9% Max. from 100% to 0% or from 0% to 100% Linear Load
Rated Current at 240 V 9.6 A
Overload Capacity 125% for 1 Minute; 150% for 30 Seconds
Crest Factor 2.5 at Full Load
Frequency 50/60 Hz Auto-Sensing (± 0.5 Hz)
Wave Form Sine Wave, Zero Transfer Time
Load Power Factor 0.7
Efficiency AC to DC to AC 80%
BATTERY
DC Voltage 48V
Backup Time (Full Load) 7 Minutes
Battery Type Enersys NPX-35FR Lead Acid 9 Ah/12 V
Number of Batteries Two (2) Strings in Parallel, Four (4) Batteries per String
PHYSICAL
Interface RS-232, Dry Contact, External Battery Connectors
Line Cord and Receptacles Hardwired (With Optional Line Cord & Receptacle Panels)
Dimensions 254 W x 686 D x 597 H mm (10 W x 27 D x 23.5 H in.)
Weight 77 kg (170 lbs.)
OPTION
Network Interface Card RemotEye®II Part #: RMTI-INT-R4
Environmental Monitoring Device Part #: RMTI-EMD-HT
ENVIROMENT
Operating Ambient Temperature 0 to 40° C (32 to 104° F)
Humidity 30% to 90%, Non-Condensing
Audible Noise Less than 50 dB Normal and Battery Modes
Altitude 1000 m (3000 ft) Above Sea Leve
CONFORMANCE
Regulatory Approvals UL1778, CUL, CE, FCC Class A, IEEE 587, ANSI/C62.41, ISO 9001, ISO 140001, NEMA/PE1-1993
Warranty Three (3) Years on Electronics Two (2) Years Full Replacement on Batteries (See Toshiba Warranty Policy for Full Details)
*208/240 Transformer Models Result in 5% Derating
1. Due to continuous product improvements, program specifications are subject to change without notice.