Three Phase TOSHIBA 4200FA CT Series
4200FA CT Series
TOSHIBA 4200FA CT Series

The 4200FA CT Series high efficiency UPS unit is today's choice for highest design quality at the most competitive price points available. The 4200FA CT Series has the largest input voltage/frequency window in the industry. This allows for the unit to be user friendly to the batteries, thus extending the life of battery. The front end IGBT design allows it to work optimally at 0-100% load with low less than 3% THD on the input. This allows for one to one sizing of the Generator. The 4200FA CT Series also offers a Standard Three Year Warranty.

The CT models are designed for internal batteries and internal maintenance bypass design without the need for additional cabinets.

Features & Benefits

• True On-Line Double Conversion UPS

• Input Power Factor > 0.99

• Input Current THD < 3%

• Wide Input Voltage Window +20% to -30%

• Wide Input Frequency Window 45 to 65 Hz

• All IGBT 16 kHz Design (Rectifier/DC Converter/Inverter)

• Electronic Power Factor Correction for 100% Generator Compatibility

• Complete Front Access for Installation, Operation, and Service

• Internal Batteries

• Internal Maintenance Bypass Switch

• 100% Unbalanced Load Capability

• SNMP/Web-Based Monitoring

4200FA CT Series UPS STatic Bypass
TOSHIBA 4200FA CT Series UPS Technical Specifications (15kVA-50kVA)
MODEL NUMBER T42F3F150XAMBN T42F3F250XAMBN T42F3F300XAMBN T42F3F500XAMBN
CAPACITY
kVA/kW 15/12 25/20 30/24 50/40
TOPOLOGY True On-Line, Double-Conversion, IGBT PWM, with Active Input Power Factor Correction
INPUT
Voltage 208/120 V, Three-Phase, Four-Wire + Ground
Voltage Range +10% to -30%; +20% to -30% Online (Without Utilizing Battery)
Power Factor Greater than 0.99
Current THD Less than 3%
Frequency 50/60 Hz (Range 45 to 65 Hz)
Current Limit 115% Maximum
OUTPUT
Voltage 208/120 V, Three-Phase, Four-Wire + Ground
Frequency 50/60 Hz ± 0.01% (Can be Used as Frequency Converter)
Voltage Regulation <1% Balanced, 100% Load Step/<2% Unbalanced, 100% Load Step
Overload (Inverter) 125% for 90 Seconds; 150% for 30 Seconds
Overload (Bypass) 125% for 10 Minutes; 1000% for 10 Minutes per Second
BATTERY
Time (Full/Half load) 9/26 Minutes 4/13 Minutes 3/10 Minutes 4.5/14 Minutes
DC Link 288 VDC
Ripple Voltage < 0.5% DC
ENVIROMENT
Temperature Range 0° to 40°C Operating/-20° to +50°C Storage
Relative Humidity 0 to 95% Non-Condensing
Heat Rejection 8988 BTUs 12,043 BTUs 14,451 BTUs 18,611 BTUs
Efficiency 82% AC-AC
86% DC-AC
85% AC-AC
87% DC-AC
88% AC-AC
89% DC-AC
89% AC-AC
88% DC-AC
DIMENSIONS
Dimensions (LxDxH) 20” x 36.3” x 59.8” 35.5” x 38.3” x 59.3”
Weight (lbs.) 900 910 915 2548
Altitude 6600 ft. (2000 m) (Maximum Without Derating)
Audible Noise < 60 DBA at 1 m < 65 DBA at 1 m
FEATURES Internal Make-Before-Break Maintenance Bypass Switch, RS232, and Dry Contact Interface
STANDARDS UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), NEMA PE1-1993
WARRANTY See Toshiba Warranty Policy for Full Details
1. Due to continuous product improvements, program specifications are subject to change without notice.