Three Phase TOSHIBA 4200FA XT Series UPS
TOSHIBA 4200FA XT Series UPS
TOSHIBA 4200FA XT Series UPS

The 4200FA XT Series high efficiency UPS unit is today's choice for highest design quality at the most competitive price points available. The 4200FA XT Series has the largest input voltage/frequency window in the industry. This allows for the unit to be user friendly to the batteries, thus extending the life of battery. The front end IGBT design allows it to work optimally at 0-100% load with low less than 3% THD on the input. This allows for one to one sizing of the Generator.

The 4200FA XT Series also offers a Standard Three Year Warranty. The XT model allows for internal isolation transformers built in the cabinet. The XT is built for extreme conditions and a large variety of three phase voltage applications.

Features & Benefits

• True on-Line double conversion UPS

• Input power factor > 0.99

• Input current THD < 3%

• Wide input voltage window +20% to -30%

• Wide input frequency window 45 to 65 Hz

• All IGBT 12 kHz design (Rectifier/DC Converter/Inverter)

• Electronic power factor correction for 100% generator Compatibility

• Complete front access for installation, operation, and service

• External battery options for customized battery back-up time

• XT Series is designed for extreme applications

• Internal isolation transformer(s)

• Internal maintenance bypass switch*

• 100% Unbalanced load capability

• SNMP/Web-based monitoring

TOSHIBA 4200FA XT Series (15-80kVA) UPS Systems
Model Number T42X3X150XAMXN T42X3X250XAMXN T42X3X300XAMXN T42X3X500XAMXN T42X3X800XAXXN
CAPACITY
kVA/kW 15/12 25/20 30/24 50/40 80/64
TOPOLOGY True On-line, Double Conversion, IGBT PWM, with Active Input Power Factor Correction
INPUT
Voltage 208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 3 w + Gnd
Voltage Range +10% to -30%; +20% to -30% Online (Without Utilizing Battery)
Power Factor Greater than 0.99
Current THD Less than 3%
Frequency 50/60 Hz (range 45 to 65 Hz)
Current Limit 115% maximum
OUTPUT
Voltage 208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 4 w + Gnd
Frequency 50/60 Hz ± 0.01% (Can be Used as a Frequency Converter)
Voltage Regulation < 1% balanced, 100% load step; < 2% unbalanced, 100% load step
Overload (inverter) 125% for 90 sec, 150% for 30 sec
Overload (bypass) 125% for 10 min, 1,000% for 10 ms
BATTERY
DC Link 288 VDC
Ripple VoltageE <.5% DC
ENVIRONMENT
Temperature Range 0 to 40°C (operating)/-20 to +50°C (storage)
Relative Humidity 0 to 95% non condensing
Heat Rejection 5,733 BTUs 7,600 BTUs 9,100 BTUs 17,737 BTUs 24,270 BTUs
Efficiency AC/DC/AC 87.7%, DC/AC 90% AC/DC/AC 88.5% AC/DC/AC 90%
DIMENSIONS
Dimensions (LxDxH) 20" x 36.3" x 59.8" 35.6" x 37.6" x 59.8" 44" x 31" x 74"
(1/2) TRANSFORMER(S)
UPS Weight (lb) 1,275/1,475 1,275/1,475 1,275/1,475 1,581/1,941 2,450
Altitude 6,600 ft (2000 m) (Maximum Without Derating)
Audible Noise <60 dBA at 1m < 65 dBA at 1 m < 65 dBA at 1 m
FEATURES Internal Make-before-break Maintenance Bypass Switch*, RS232 and Dry Contact Interface
OPTIONS Dual Input Feed, Air Filters for Door, RemotEye II®
STANDARDS UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), NEMA PE1-1993
WARRANTY (See Toshiba Warranty Policy for Full Details.)
SERVICE 7 x 24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)