Three Phase TOSHIBA G8000 Series 1
TOSHIBA G8000 Series UPS (80 to 300kVA)
Three Phase TOSHIBA G8000 Series 2
TOSHIBA G8000 Series UPS Open(80 to 300kVA)
« »
TOSHIBA G8000 Series UPS

The G8000 Series UPS is widely used in the medical industry where power protection is critical. The G8000 Series offers unity power factor output which provides 20% more power than other UPS manufacturers. It is also 100% generator compatible, and its low input current harmonics eliminates the need for an oversized generator. In addition, the high crest factor is ideal for medical equipment including MRIs and CT Scanners which have a high current inrush.

Features & Benefits

• Input Power Factor > 0.99

• Output Power Factor 1.0

• Input Current THD < 5%

• Internal Isolation Transformer

• 208 V Output Models Available

• True Online, Double-Conversion UPS

• 100% Unbalanced Load Capability

• Electronic Battery Isolation for Battery Longevity

• Complete Front-Access for Installation, Operation, and Service

• XT Series Designed for Extreme Applications (Harsh Environments)

• External Battery Options for Customized Battery Backup Time

• IGBT DC Converter/Inverter Design

• Generator-Friendly Design and Compatibility

• SNMP/Web-Based Monitoring

• Flywheel Compatible

• Assembled in USA

TOSHIBA G8000 Series UPS
MODEL # T80S3K08KK 6XS2H T80S3K10KK 6XS2H T80S3K15KK 6XSNH T80S3K22KK 6XSNH T80S3K30KK 6XSNH
INPUT
Rated Output Capacity 80 KVA/80 KW 100 KVA/ 100 KW 150 KVA/150 KW 225 KVA/ 225 KW 300 KVA / 300 KW
Voltage 480 VAC (+10% to -15%)
Frequency 60 Hz (+/-5%)
Configuration 3 Phase; 3 Wire + GND
Input KW 90kW 110kW 165kW 247kW 318kW
(102kW Charging) (122 KW Charging) (181 KW Charging) (270 KW Charging) (319 KW Charging)
Power Factor > 0.99 PF Lagging
Walk-In Function EEPROM Upgrade
Maximum Input Current 108 A Normal 135 A Normal 200 A Normal 303 A Normal 396 A Normal
(125 A Charging) (150 A Charging) (222 A Charging) (338 A Charging) (401 A Charging)
Reflected THD < 5% Maximum @ 100% Load
6% Maximum @ 25% Load
BYPASS
Configuration Three-Phase; Four-Wire + Ground
Voltage 480/277V (?10%)
Frequency 60 Hz (?5%)
Bypass Overload Capacity 1000% for One Cycle, 500% for Two Cycles
BATTERY BACKUP
Number of Cells 180
Type Lead Acid (Contact Factory for Alternative Options)
DC Nominal 360 V
DC Minimum 288 V
Float Charge 405 V
Ripple Current (without batteries) AC Ripple on DC Bus: < 0.2% of DC Voltage
Back-up Time Application Specific
Max DC Charging Current 30A 30A 30A 30A 30A
Max Discharge 305 375 566 840 1120
OUTPUT
Voltage 480Y/277V
Configuration Three-Phase; Four-Wire + Ground
Voltage Regulation ?1% for 0 to 100%Balanced and Unbalanced Loads
Voltage Adjustment Range ?5% (In Increments of 1V)
Voltage Unbalance ?3% for 100% Linear Loads ?5% for 100% Non-Linear Loads
Crest Factor 2
Transient Voltage Response ?2% Maximum with a 100% Step Loads (Without Utilizing Batteries)
?1.5% Maximum with Loss/Return AC Input
?2% Maximum When Load Transfers To/From Bypass
Transient Recovery ime <50 ms
Frequency 60 Hz
Frequency Synchronous Range ?0.5 Hz, ?1 Hz, + 1.5Hz (Selectable)
Frequency Slew Rate 1 Hz/Sec
Frequency Regulation ?0.01% in free running mode
Current 96 A 120 A 180 A 271 A 361 A
Power Factor 1.0 PF Lagging: 32 - 86 °F (0 - 30 °C) 0.8 PF Lagging: 86 - 104 °F (30 - 40 °C)
Overload Capacity 125% for 10 Minutes, 150% for 60 Seconds
Voltage THD < 3% Max with 100% Linear Load/5% Max with 100% Non-Linear Load
Withstanding Rating 65 KA (With Optional Fuse)
RELIABILITY
MTBF 200,000 Hours
EFFICIENCY
@ 25% Load 83.9% 86.4% 89.6% 87.9% 88.8%
@ 50% Load 85.3% 90.1% 91.7% 91.0% 91.7%
@ 75% Load 90.0% 91.2% 92.3% 92.3% 92.7%
@ 100% Load 90.6% 91.0% 93.0% 91.9% 92.0%
ENVIROMENT
Cooling Forced Air
Paint Color Sherwin Williams HHT2-7055, 079 Beige Texture
Weight 1390lb. (630 kg) 1740 lb. (789 kg) 2467 lb. (1119kg) 2980 lb. (1352 kg) 4575 lb. (2075 kg)
Weight (Shipping) 1440 lb. (653 kg) 1790 lb. (812 kg) 2556 lb. (1159 kg) 3069 lb. (1392 kg) 4725 lb. (2143 kg)
Floor Loading 171 Lbs/ft? (1037 kg/m2) 214 Lbs/ft? (1299 kg/m2) 203 Lbs/ft? (991 kg/m2) 245 Lbs/ft? (1196 kg/m2) 255 Lbs/ft? (1245 kg/m2)
Dimension - Width 36.8 in. (935 mm) 55.1 in. (1400 mm) 76.8 in. (1951 mm)
Depth 32.5 in. (826 mm) 31.8 in. (808 mm) 35.7 in. (907 mm)
Height 79.2 in. (2012 mm) 79.4 in. (2017 mm)
Power Cable Access Bottom Access Top or Bottom Access Top Access
Operating Temperature 32° to 86°F (0° to 30°C) for 1.0 PF 32° to 104°F (0° to 40°C) for 0.8 PF
Operating Humidity 30% to 90% Non-Condensing
Operating Altitude 3200 Feet (1000 m)
MONITORING
Warranty Three Years Parts and Labor
Intelligent Monitoring (Optional) SNMP; Modbus RTU; Modbus TCP; BACNET, METASYS
Display LCD Touch-Panel for Local Monitoring, Operation, and Control
1. Due to continuous product improvements, program specifications are subject to change without notice.

* = estimated data. Consult factory for updated information.